MGate EIP3170/MGate EIP3270 Series

• Ethernet Interface
Protocols CIP (PCCC) on EtherNet/IP
Number of Ports 2 (1 IP, supports Ethernet cascading)
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol DF1 Full-duplex
Number of Ports EIP3170/3170I: 1
EIP3270/3270I: 2
Serial Standards RS-232/422, software selectable
Connectors EIP3170/3170I: DB9 male for RS-232, terminal block for RS-422
EIP3270/3270I: DB9 male x 2
ESD Protection 15 kV for all signals
• Serial Communication Parameters
Data Bits 8
Stop Bits 1, 2
Parity None, Even, Odd
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 1200 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
• Software
Configuration Options Serial Console, Telnet Console, Windows Utility
Utility MGate Manager for Windows 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2
Support Smart Routing, Serial Redirection, ProCOM, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Plastic, IP30
Weight MGate EIP3170: 360 g (0.79 lb)
MGate EIP3270: 380 g (0.84 lb)
Dimensions Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Vibration IEC 60068-2-6, IEC 60068-2-64
Shock IEC 60068-2-27
Drop IEC 60068-2-32
• Power Requirements
Input Voltage 12 to 48 VDC
Input Current MGate EIP3170: 435 mA @ 12 VDC
MGate EIP3170I: 555 mA @ 12 VDC
MGate EIP3270: 435 mA @ 12 VDC
MGate EIP3270I: 510 mA @ 12 VDC
Power Connector Terminal block
Relay Output 1 digital relay output to alarm (normal close); Current carrying capacity: 1 A @ 30 VDC
• Standards and Certifications
Safety UL 508, EN 60950-1
Hazardous Location Class 1 Division 2, ATEX, IECEx
EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV
IEC 61000-4-5 Surge: Power: 4 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m
IEC 61000-4-8 PFMF
IEC 61000-4-11
• MTBF (mean time between failures)
Time MGate EIP3170: 1,344,456 hrs
MGate EIP3270: 1,204,573 hrs
Standard Telcordia SR332
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty