• ioLogik E2214 Specifications | |
• Inputs and Outputs | |
Digital Inputs | 6 channels |
Relay Outputs | 6 channels |
Isolation | 3k VDC 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN PNP) and Dry Contact |
I/O Mode | DI Event Counter |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to GND) | • On: 0 to 3 VDC • Off: 10 to 30 VDC |
Common Type | 3 points per COM |
Counter Frequency | 900 Hz |
Digital Filtering Time Interval | Software Configurable |
• Relay Output | |
Type | Form A (N.O.) power relay |
Contact Current Rating | • Inductive Load: 2 A @ 30 VDC, 250 VAC, 110 VAC • Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC |
Minimum permitted load | 1 A @ 5 VDC |
Initial Insulation Resistance | 1000 mega-ohms (min.) @ 500 VDC |
Mechanical Endurance | 1,000,000 operations |
Electrical Endurance | 100,000 operations @ 5 A resistive load |
Contact Resistance | 100 milli-ohms (max.) |
Pulse Output | 0.3 Hz at rated load |
Note | Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik E2214 may malfunction when operating in high condensation environments below 0° Celsius. |
• Power Requirements | |
Input Voltage | 12 to 36 VDC |
Input Current | 170 mA @ 24 VDC |
• MTBF (mean time between failures) | |
Time | 307,239 hrs |
Standard | Telcordia SR332 |
• Common Specifications | |
• LAN | |
Ethernet | 1 10/100 Mbps RJ45 port |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP |
• Serial | |
Interface | 1 RS-485-2w terminal block port |
Parity | None |
Data Bits | 8 |
Stop Bits | 1 |
Flow Control | None |
Baudrate | 1200 to 115200 bps |
Protocols | Modbus RTU (gateway) |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
Weight | under 250 g (0.55 lb) |
Mounting | DIN-rail wall |
• Environmental Limits | |
Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | Up to 2000 m |
Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 61000-6-2/6-4 |
EMI | CISPR 22, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m 1.4 GHz to 2 GHz: 3 V/m 2 GHz to 2.7 GHz: 1 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000- |
Green Product | RoHS, CRoHS, WEEE |
Note | Please check Moxa’s website for the most up-to-date certification status. |
• Warranty | |
Warranty Period | 2 years |
Details | See www.moxa.com/warranty |
*Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty.