ioLogik R2140

Features and Benefits

  • 8 analog input channels for millivolts (mV), voltage, and current signal with wire-off detection (at 4 to 20 mA)
  • 2-channel analog outputs for voltage, current actuator control
  • 16-bit resolution analog inputs, 12-bit resolution analog output
  • Simplify I/O management with MXIO library on Windows  Linux platform
  • Firmware upgradable over RS-485

 

• Serial Communication
Interface RS-485-2w: Data+, Data-, GND (3-contact terminal block)
Serial Line Protection 15 kV ESD for all signals
• Serial Communication Parameters
Parity None
Data Bits 8
Stop Bits 1
Flow Control None
Baudrate 9600 to 115200 bps
Protocols Modbus/RTU
• Inputs and Outputs
Analog Inputs 8 channels
Isolation 3K VDC  2K Vrms
Analog Outputs 2 channels
• Analog Input
Resolution 16 bits
I/O Mode Voltage / Current
Input Range ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA,4 to 20 mA
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Sampling Rate (for current)
All channels: 6 samples/sec
• Per channel: 0.75 samples/sec
• Only one channel enabled: 0.75 samples/sec
Input Impedance 900 kΩ
Built-in Resistor for Current Input 106 ohms
• Analog Output
Resolution 12 bits
Output Range 0 to 10 V, 4 to 20 mA
Drive Voltage 15 VDC for current output
Accuracy ±0.1% FSR @ 25°C,
±0.3% FSR @ -10 and 60°C
Load Resistor Less than 250 ohms
• Power Requirements
Power Input 24 VDC nominal, 12 to 48 VDC
Power Consumption 170 mA @ 24 VDC
• Physical Characteristics
Wiring I/O cable max. 14 AWG
Dimensions 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
Note: Please see pages 14-26 for this product’s dimensions diagram.
Weight 200 g
Mounting DIN rail  wall
• Environmental Limits
Operating Temperature -10 to 60°C (14 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMI EN 61000-3-2; EN 61000-3-3;
EN 61000-6-4; FCC Part 15, Subpart B, Class A
EMS EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8,
EN 61000-4-11, EN 61000-6-2
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Green Product RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up-to-date certification status.
• MTBF (mean time between failures)
Time 280,923 hrs
Standard Telcordia (Bellcore)
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty