• Inputs and Outputs | |
Configurable DIOs (by software) | 12 channels |
Analog Inputs | 4 channels |
Isolation | 3k VDC 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN PNP) and Dry Contact |
I/O Mode | DI Event Counter |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to COM) | • On: 10 to 30 VDC • Off: 0 to 3 VDC |
Common Type | 6 points per COM |
Counter Frequency | 2.5 kHz |
Digital Filtering Time Interval | Software configurable |
• Digital Output | |
Type | Sink |
I/O Mode | DO Pulse Output |
Pulse Output Frequency | 5 kHz |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 1.5 A per channel @ 25°C |
Over-Temperature Shutdown | 175°C (min.) |
Current Rating | 500 mA per channel @ 25°C |
DIO Output Leakage Current | < 1 mA @ 30 VDC |
• Analog Input | |
Type | Differential input |
Resolution | 16 bits |
I/O Mode | Voltage / Current (software selectable) |
Input Range | ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA (burnout detection) |
Accuracy | • ±0.1% FSR @ 25°C • ±0.3% FSR @ -10 and 60°C • ±0.5% FSR @ -30 and 70°C |
Sampling Rate | • All channels: 400 samples/sec • Per channel: 100 samples/sec |
Input Impedance | 1M ohms (min.) |
Built-in Resistor for Current Input | 120 ohms |
• Power Requirements | |
Input Voltage | 9 to 48 VDC |
Input Current | 442 mA @ 24 VDC |
• MTBF (mean time between failures) | |
Time | 378,154 hrs |
Standard | Telcordia SR332 |
• Common Specifications | |
• Cellular | |
Standards | GSM/GPRS/EDGE/UMTS/HSPA+ |
HSPA Model Band Options | • UMTS/HSPA+: five-band 800/850/900/1900/2100 MHz • GSM/GPRS/EDGE: quad-band 850/900/1800/1900 MHz |
GPRS Model Band Options | GSM/GPRS/EDGE: quad-band 850/900/1800/1900 MHz |
SIM Control Voltage | 3/1.8 V |
SIM Format | Full size |
• LAN | |
Ethernet | • 4 switched 10/100 Mbps RJ45 ports • 1 optimized port for faster downstream communications with daisy-chained ioLogik E1200 units |
Note | The optimized daisy-chain port is not supported by the ioLogik E1261W-T, E1261H-T, E1263H-T. |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP |
• Serial | |
Interface | 2 RS-232/422/485 (software selectable) RJ45 ports |
Parity | None, Odd, Even |
Data Bits | 5, 6, 7, 8 |
Stop Bits | 1, 2 |
Flow Control | None, RTS/CTS, XON/XOFF |
Baudrate | 300 to 115200 bps |
Protocols | Modbus/RTU (master/gateway), serial tunnel mode (client/server) |
• Physical Characteristics | |
Wiring | I/O cable, 14 AWG (max.) |
Dimensions | 61 x 157 x 115 mm (2.4 x 6.18 x 4.53 in) |
Weight | Under 1265 g (2.79 lb) |
Mounting | DIN rail (standard), wall (optional) |
• Storage | |
Expansion Slot | Up to 32 GB microSD™ memory card (SDHC compatible) |
Note | For units operating in extreme temperatures, industrial-grade, wide-temperature SD cards are required. |
• Environmental Limits | |
Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -30 to 70°C (-22 to 158°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | Up to 2000 m |
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. | |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 61000-6-2/6-4 |
EMI | FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power 2 kV IEC 61000-4-6 CS: 3 V IEC 61000-4-8 |
Radio | R&TTE: EN 62311, EN 300 328, EN 301 489-1, EN 301 489-17, EN 301 893; NCC; VCCI |
Hazardous Location | Class 1 Division 2; ATEX Zone 2 |
Green Product | RoHS, CRoHS, WEEE |
Note: Please check Moxa’s website for the most up-to-date certification status. | |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
MOXA, Smart Remote I/O
ioLogik 2542-HSPA
Features and Benefits
- Front-end intelligence with Click&Go Plus control logic, up to 48 rules
- Active communication with MX-AOPC UA Server
- Automatically complement disconnection period data with MX-AOPC UA Logger software
- 4-port unmanaged switch built in for linking to Ethernet devices
- I/O expansion port for daisy chaining up to 8 ioLogik E1200 units
- 3-in-1 RS-232/422/485 serial port for connecting to serial devices in the field
- Supports SNMPv1/v2c/v3
- Simplify I/O management with MXIO library for Windows Linux platforms
- Wide operating temperature range of -30 to 70°C (-22 to 158°F)