• ioLogik E1212 Specifications | |
• Inputs and Outputs | |
Digital Inputs | 8 channels |
Configurable DIOs (by jumper) | 8 channels |
Isolation | 3k VDC 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN PNP), Dry Contact |
I/O Mode | DI Event Counter |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to COM) | • On: 10 to 30 VDC • Off: 0 to 3 VDC |
Common Type | 8 points per COM |
Counter Frequency | 250 Hz |
Digital Filtering Time Interval | Software Configurable |
• Digital Output | |
Type | Sink |
I/O Mode | DO Pulse Output |
Pulse Output Frequency | 500 Hz |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
Current Rating | 200 mA per channel |
• Power Requirements | |
Input Voltage | 12 to 36 VDC |
Input Current | 155 mA @ 24 VDC |
• MTBF (mean time between failures) | |
Time | 561,930 hrs |
Standard | Telcordia SR332 |
• Common Specifications | |
• LAN | |
Ethernet | 2 switched 10/100 Mbps RJ45 ports |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP (Slave), EtherNet/IP*, SNMPv1/v2c, RESTful API, TCP/IP, UDP, DHCP, BOOTP, HTTP |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
Weight | Under 200 g (0.44 lb) |
Mounting | DIN rail wall |
• Environmental Limits | |
Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | Up to 2000 m |
Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 55032, EN 55024, EN 61000-3-2/3-3, EN 61000-6-2/6-4 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 |
Hazardous Location | Class 1 Division 2, ATEX Zone 2 |
Green Product | RoHS, CRoHS, WEEE |
Note: Please check Moxa’s website for the most up-to-date certification status. | |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
MOXA, Remote I/O
ioLogik E1212
-
User-definable Modbus/TCP Slave addressing
- Supports EtherNet/IP* adapter mode
- Supports RESTful API for IIoT applications
- 2-port Ethernet switch for daisy-chain topologies
- Save time and wiring cost with peer-to-peer communications
-
Active communications with MX-AOPC UA Server
-
Supports SNMPv1/v2c
-
Easy mass deployment and configuration with ioSearch utility
-
Friendly configuration via web browser
-
Simplify I/O management with MXIO library on either a Windows Linux platform
-
Class I Division 2, ATEX Zone 2 certification
-
Wide operating temperature range: -40 to 75°C (-40 to 167°F)