ioLogik E1213

 

  • User-definable Modbus/TCP Slave addressing
  • Supports EtherNet/IP* adapter mode
  • Supports RESTful API for IIoT applications
  • 2-port Ethernet switch for daisy-chain topologies
  • Save time and wiring cost with peer-to-peer communications
  • Active communications with MX-AOPC UA Server
  • Supports SNMPv1/v2c
  • Easy mass deployment and configuration with ioSearch utility
  • Friendly configuration via web browser
  • Simplify I/O management with MXIO library on either a Windows   Linux platform
  • Class I Division 2, ATEX Zone 2 certification
  • Wide operating temperature range: -40 to 75°C (-40 to 167°F)

 

Description

• ioLogik E1213 Specifications
• Inputs and Outputs
Digital Inputs 8 channels
Digital Outputs 4 channels
Configurable DIOs (by jumper) 4 channels
Isolation 3k VDC  2k Vrms
• Digital Input
Sensor Type Wet Contact (NPN  PNP), Dry Contact
I/O Mode DI  Event Counter
Dry Contact • On: short to GND
• Off: open
Wet Contact (DI to COM) • On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type 12 points per COM
Counter Frequency 250 Hz
Digital Filtering Time Interval Software configurable
• Digital Output
Type Source
I/O Mode DO  Pulse Output
Pulse Output Frequency 500 Hz
Over-Voltage Protection 41 VDC
Over-current Protection 1.5 A per channel @ 25°C
Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Current Rating 500 mA per channel
• Power Requirements
Output Voltage Rating 15 to 30 VDC (12  9 VDC configurable by jumper on the 4 DO channels)
Input Voltage 12 to 36 VDC
Input Current 130 mA @ 24 VDC
• MTBF (mean time between failures)
Time 715,256 hrs
Standard Telcordia SR332
• Common Specifications
• LAN
Ethernet 2 switched 10/100 Mbps RJ45 ports
Protection 1.5 kV magnetic isolation
Protocols Modbus/TCP (Slave), EtherNet/IP*, SNMPv1/v2c, RESTful API, TCP/IP, UDP, DHCP, BOOTP, HTTP
• Physical Characteristics
Wiring I/O cable max. 14 AWG
Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight Under 200 g (0.44 lb)
Mounting DIN rail  wall
• Environmental Limits
Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Altitude Up to 2000 m
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMC EN 55032, EN 55024, EN 61000-3-2/3-3, EN 61000-6-2/6-4
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8
Hazardous Location Class 1 Division 2, ATEX Zone 2
Green Product RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up-to-date certification status.
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty