ioLogik E2262

Features and Benefits

  • Front-end intelligence with patented Click&Go control logic, up to 24 rules
  • Active communication with MX-AOPC UA Server
  • Save time and wiring cost with peer-to-peer communication
  • Supports SNMPv1/v2c/v3
  • Friendly configuration via web browser
  • Simplify I/O management with MXIO library for Windows Linux platforms
  • Wide operating temperature range of -40 to 75°C (-40 to 167°F)

Description

• ioLogik E2262 Specifications
• Inputs and Outputs
Digital Outputs 4 channels
Thermocouples 8 channels
• Digital Output
Isolation 3k VDC  2k Vrms
Type Sink
I/O Mode DO  Pulse Output
Pulse Output Frequency 100 Hz
Over-Voltage Protection 45 VDC
Over-Current Protection 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown 175°C
Current Rating 200 mA per channel
• Thermocouple
Sensor Type J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
Millivolt Type • Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
Sampling Rate All channels: 12 samples/sec
Per channel: 1.5 samples/sec
Resolution 16 bits
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Input Impedance 1 mega-ohm ohms
• Power Requirements
Input Voltage 12 to 36 VDC
Input Current 160 mA @ 24 VDC
• MTBF (mean time between failures)
Time 341,063 hrs
Standard Telcordia SR332
• Common Specifications
• LAN
Ethernet 1 10/100 Mbps RJ45 port
Protection 1.5 kV magnetic isolation
Protocols Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP
• Serial
Interface 1 RS-485-2w terminal block port
Parity None
Data Bits 8
Stop Bits 1
Flow Control None
Baudrate 1200 to 115200 bps
Protocols Modbus RTU (gateway)
• Physical Characteristics
Wiring I/O cable max. 14 AWG
Dimensions 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
Weight under 250 g (0.55 lb)
Mounting DIN-rail  wall
• Environmental Limits
Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Altitude Up to 2000 m
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMC EN 61000-6-2/6-4
EMI CISPR 22, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS:
80 MHz to 1 GHz: 10 V/m
1.4 GHz to 2 GHz: 3 V/m
2 GHz to 2.7 GHz: 1 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-
Green Product RoHS, CRoHS, WEEE
Note Please check Moxa’s website for the most up-to-date certification status.
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty