ioLogik R1214

Features and Benefits

  • Dual RS-485 remote I/O with built-in repeater
  • Supports the installation of multidrop communications parameters
  • Install communications parameters and upgrade firmware via USB
  • Upgrade firmware through an RS-485 connection
  • Wide operating temperature range: -40 to 85°C (-40 to 185°F)
ioLogik R1214 Specifications
• Inputs and Outputs
Digital Inputs 6 channels
Relays 6 channels
Isolation 3k VDC  2k Vrms
• Digital Input
Sensor Type Wet Contact (NPN  PNP), Dry Contact
I/O Mode DI  Event Counter
Dry Contact • On: short to GND
• Off: open
Wet Contact (DI to COM) • On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type 6 points per COM
Counter Frequency 2.5 kHz
Digital Filtering Time Interval Software Configurable
• Relay
Type Form A (N.O.) power relay
Contact Current Rating Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage 500 VAC
Relay On/Off Time 1500 ms (max.)
Initial Insulation Resistance 1000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance 5,000,000 operations
Electrical Endurance 100,000 operations @ 5 A resistive load
Contact Resistance 100 milli-ohms (max.)
Pulse Output 0.3 Hz at rated load
Note: Ambient humidity must be non-condensing and remain between 5 and
95%. The relays of the ioLogik R1214 may malfunction when operating in high condensation environments below 0°C.
• Power Requirements
Input Voltage 12 to 48 VDC
Input Current 207 mA @ 24 VDC
Common Specifications
• Serial
Interface 2 RS-485-2w terminal block ports
Serial Line Protection • ESD Protection: 15 kV
• Surge Protection: 1 kV
• High/Low Resistor for RS-485: 1 kΩ, 150 kΩ
Parity None, Even, Odd
Data Bits 8
Stop Bits 1, 2
Baudrate 1200 to 921600 bps
Protocols Modbus RTU (slave)
• Physical Characteristics
Wiring I/O cable max. 16 AWG
Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight Under 200 g (0.44 lb)
Mounting DIN-rail  wall
• Environmental Limits
Operating Temperature Standard Models: -10 to 75°C (14 to 167°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Altitude Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV
IEC 61000-4-6 CS: 3 V
IEC 61000-4-8
Green Product RoHS, CRoHS, WEEE
Please check Moxa’s website for the most up-to-date certification status.
• MTBF (mean time between failures)
Time 1,239,293 hrs
Standard Telcordia SR332
• Warranty
Warranty Period 5 years (excluding the ioLogik R1214)
Details See www.moxa.com/warranty
Note: Because of the limited lifetime of power relays, products that use this
component are covered by a 2-year warranty.
Scroll to Top
โทรเลย !