ioLogik R1241

Features and Benefits

  • Dual RS-485 remote I/O with built-in repeater
  • Supports the installation of multidrop communications parameters
  • Install communications parameters and upgrade firmware via USB
  • Upgrade firmware through an RS-485 connection
  • Wide operating temperature range: -40 to 85°C (-40 to 185°F)
ioLogik R1241 Specifications
• Inputs and Outputs
Analog Outputs 4 channels
Isolation 3k VDC  2k Vrms
• Analog Output
Resolution 12 bits
Output Range 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA
Voltage Output 10 mA (max.)
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Load Resistor Internal register: 400 ohms
Note: 24 V of external power required when loading exceeds 1000 ohms.
• Power Requirements
Input Voltage 12 to 48 VDC
Input Current 343 ma @ 24 VDC
Common Specifications
• Serial
Interface 2 RS-485-2w terminal block ports
Serial Line Protection • ESD Protection: 15 kV
• Surge Protection: 1 kV
• High/Low Resistor for RS-485: 1 kΩ, 150 kΩ
Parity None, Even, Odd
Data Bits 8
Stop Bits 1, 2
Baudrate 1200 to 921600 bps
Protocols Modbus RTU (slave)
• Physical Characteristics
Wiring I/O cable max. 16 AWG
Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight Under 200 g (0.44 lb)
Mounting DIN-rail  wall
• Environmental Limits
Operating Temperature Standard Models: -10 to 75°C (14 to 167°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Altitude Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV
IEC 61000-4-6 CS: 3 V
IEC 61000-4-8
Green Product RoHS, CRoHS, WEEE
Please check Moxa’s website for the most up-to-date certification status.
• MTBF (mean time between failures)
Time 1,239,293 hrs
Standard Telcordia SR332
• Warranty
Warranty Period 5 years (excluding the ioLogik R1214)
Details See www.moxa.com/warranty
Note: Because of the limited lifetime of power relays, products that use this
component are covered by a 2-year warranty.
Scroll to Top