• LAN | |
Ethernet | 1 x 10/100 Mbps, RJ45 |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP, SNTP |
• Digital Input | |
Channels | 8, source type |
Sensor Type | NPN, Dry contact |
I/O Mode | Digital Input |
Dry Contact | • Logic 0: short to GND • Logic 1: open |
Wet Contact | • Logic 0: 0 to 3 VDC • Logic 1: 10 to 30 VDC (DI COM to DI) |
Common Type | 8 points per COM |
Isolation | 3K VDC 2K Vrms |
Digital Filtering Time Interval | Software selectable |
Over-Voltage Protection | 36 VDC |
• Digital Output | |
Channels | 8, sink type, 36 VDC, 200 mA |
I/O Mode | Digital Output |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 600 mA |
Over-Temperature Shutdown | 160°C |
Output Current Rating | Max. 200 mA per channel |
Isolation | 3k VDC 2k Vrms |
• Alarm Port Output | |
Channels | 1, sink type |
Output Current Rating | Max. 200 mA per channel |
Isolation | 3k VDC 2k Vrms |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 48 VDC |
DO Power | 24 VDC nominal, up to 45 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
Weight | 205 g |
• Environmental Limits | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
• Standards and Certifications | |
Safety | UL 508 |
EMI | FCC Part 15, Subpart B, Class A, EN 55022 Class A |
EMS | IEC 61000-4, IEC 61000-6 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
MOXA, Remote I/O
ioMirror E3210
Features and Benefits
- Direct input-to-output signal communication over IP
- High speed Peer-to-Peer I/O within 20 ms
- One physical alarm port for connectivity status
- Quick and easy utility and web-based settings
- Local alarm channel
- Remote alarm message
- Supports Modbus/TCP for remote monitoring
- Optional LCD module for easy configuration